Max. conductor cross-section rigid (single/multi-wire)35 mm²
Max. conductor cross-section flexible (fine-stranded)25 mm²
Protection level1.8 kV
With remote signaling contactNo
Highest continuous voltage DC545 V
Number of conductors (excluding earth)1
Network form TTYes
Network type TN-SYes
Max. discharge current (8/20)40 kA
Test class type 2Yes
Network form TNYes
Network type TN-CNo
Nominal voltage DC495 V
Network type TN-C-SYes
Short circuit strength (Isccr)100 kA
Protection level L-N1.8 kV
Network type DCNo
Protection level N-PE1.8 kV
Integrated backup fuseYes
Network type ITYes
HABOVR T2 40-440s P QS
HAN2CTB815704R4100
GTIN3660308525383
Size1 TE
Highest continuous voltage AC440V
Mounting typeDIN rail TH35
Nominal discharge current (8/20)20kA
Nominal voltage AC400V
IP protection)IP20
Signaling on the deviceOptical