Wind speed sensor, ABB i-bus KNX, physical sensors, weather center/station, linear wind speed sensor for weather station 6190/40-101. Serves to convert the recorded wind speed (0.7-40 m/s) into electrical signals (0-10 V). With PTC heating element for winter operation (in conjunction with heating transformer 6190/49). Incl. 3 m supply cable LIYY 6 x 0.25 mm. Nominal voltage: +8 V / -6 V Query voltage: 0 - 10 V- against GND at 1 kOhm minimum load Protection class (device): IP 65 Temperature range (device): -25 °C to 60 °C Dimensions (H x W x D): 160 mm x 124 mm