consisting of: Meter space, H x W (mm): 450 x 250: 3-point with sealing membrane and secondary wiring, Incl., Housing fastening set on the meter support plate (front part), Prepared for an IP54 transparent cover, APZ room, H x W (mm): 300 x 250: With LexCom Home media mounting plate and device support rail, equipped with RJ45 socket, Additional converter room, H x W (mm): 150 x 250: With perforated 3-point cover and device support rail, Without device equipment (with secondary wiring, without test terminal / voltage path fuse), Converter room, H x W (mm): 300 x 500: With insulators, Primary wiring 35mm² On Cu connection lugs and sealable cover with transparent cover, For on-site standard converter lug 170mm long in accordance with Form A according to DIN0603-2-2, hole spacing 130mm, mains-side connection area (NAR), H x W (mm): 450 x 250: with 40mm busbars, 250A, 5-pole (Cu 12 x 5mm) and empty space for overvoltage protection, mains-side disconnection point: NH00 fuse switch disconnector, 3-pole, on 40mm busbar (feed-in disconnector), sealable cover with transparent cover, including connection terminals 70mm², system-side connection area (AAR), with system-side disconnection point, H x W (mm): 450 x 250: load-break switch, 125A, 3-pole, on device mounting rail (box terminal up to 50mm²) and N+PE terminal block 50/35mm²
Property | Value |
Height: | 1205 mm |
Width: | 500 mm |
Depth: | 169 mm |
Number of DIN rails: | 2 |
Number of pitch units per DIN rail: | 12 |
With N-PE terminals: | no |
With cover: | yes |
Type of cover: | closed |
With mounting plate: | no |