HABPKZM0-16-SPI32
HAN199200
GTIN4015081972845
Design of the actuating elementRotary knob
Triggering technologyThermomagnetic
Rated operating power at AC-3, 230 V4kW
Rated operational power at AC-3, 400 V7.5kW
Rated operating voltage690V
Rated continuous current Iu16A
Rated ultimate short-circuit breaking current Icu at 400 V, AC50kA
Width45 mm
Setting range of the instantaneous short-circuit release248 A
Device typeBuilt-in device Fixed installation technology
Height102 mm
With integrated auxiliary switchNo
With integrated undervoltage releaseNo
With thermal protectionNo
Sensitive to phase failureYes
Number of poles3
IP protection)IP20
Depth75 mm
Overload release current setting16A