Number of auxiliary contacts as changeover contacts2
HABIZMX16B3-P10W-1 3-pole 1000A 42kA
HAN183471
GTIN4015081792078
Connection type main circuitRail connection
Design of the actuating elementPush button
Rated continuous current Iu1000A
Rated ultimate short-circuit breaking current Icu at 400 V, 50 Hz42kA
Rated voltage690V
Setting range of the short-time delayed short-circuit release600 to 10000 A
Setting range of the instantaneous short-circuit release2000 to 15000 A
Suitable for DIN rail mountingNo
Device typeBuilt-in device slide-in technology
DIN rail mounting optionalNo
Integrated earth fault protectionNo
Complete device with protection unitYes
With trip detectorYes
Motor drive integratedNo
Motor drive optionalYes
Number of poles3
Position of the connection for main circuitRear
IP protection)IP31
Overload release current setting400 to 1000 A