HABNZMH2-A250-FIA30-BT
HAN116306
GTIN4015081160464
Connection type main circuitFrame clamp
Design of the actuating elementRocker arm
Rated continuous current Iu250A
Rated ultimate short-circuit breaking current Icu at 400 V, 50 Hz150kA
Setting range of the instantaneous short-circuit release1500 to 2500 A
Suitable for DIN rail mountingNo
Device typeBuilt-in device Fixed installation technology
DIN rail mounting optionalYes
Integrated earth fault protectionNo
Complete device with protection unitYes
With trip detectorNo
Motor drive integratedNo
Motor drive optionalYes
Number of poles3
Position of the connection for main circuitIn front
IP protection)IP20
Overload release current setting200 to 250 A