Complete meter cabinet according to AR-N 4101:2015-09, pre-wired and equipped with switching devices. Meter field equipped with 3-point meter cross, 10mm². Lower connection compartment with 5-pin. Busbar system 12x5mm, incl. 16mm² connection terminals for accommodating selective main circuit breakers up to 63 A Functional space for additional utility company applications covered with lockable blind strip RJ45 connection socket insulated, packed loose Upper connection space with main line terminal 5x25mm², finger-safe Distribution panel with 7 x 12 TE with 2x PEN rail in plug-in technology Distribution panel equipped with: 2 pcs. PXF-40/4/003-A 12 pcs. PXL-B16/1, 2x6 circuit breakers connected to residual current device via phase rail EVG-3PHAS/N/8MODUL/LS 1 pc. Schuko sockets 230V Installation Circuit breaker rows covered with blind strip Wiring: 10mm² between main line terminal and FI/PEN rail Connection between residual current device and circuit breaker row APZ: No (retrofitting in the distribution panel below with ZSD-APZ/V1-SET possible) Protection class: IP31 Dimensions mm: Height 1100, width 550, depth 225