PROFiTEST MF TECH EVSE set for testing the effectiveness of protective measures on stationary electrical systems, particularly e-charging points after completion, repair, extension and repeat testing, particularly to comply with DGUV Regulation 3. . PROFiTEST MF TECH EVSE set with PROFiTEST MF TECH, METRALINE PRO-TYP EM II and defined accessories for testing e-charging points. With the PROFiTEST MF TECH EVSE set you are perfectly equipped for testing AC charging points for functionality and electrical safety. Context-sensitive color graphic display Measurement and test sequence - easy creation of the system structure / measure & save / generate protocol Pre-configured and self-programmable test sequences for quickly testing electrical systems Storage concept for up to 50,000 data records Testing of all current all-current sensitive RCDs, RDC-DD, RCMB Operator protection through PE detection when used by finger contact Future-oriented connectivity. Defined accessories for special measuring tasks Intuitive user guidance with help function to support upcoming measuring tasks All crucial measuring functions - can be selected quickly using a rotary switch. The compact, shock-proof housing with integrated rubber protection makes it particularly suitable for mobile use, even on construction sites and in industrial environments. The extensive setting options, including language, also make it suitable for international use Four-wire measuring technology - no compensation of the measuring cables required. The test device set is suitable for testing stationary electrical systems, in particular for e-charging points such as wall boxes and charging stations. Single- and three-phase charging points can be tested for function and electrical safety in accordance with: IEC 61581-1 (DIN0122-1) IEC 60364-4 (DIN0100-600) EN 50110-1 (DIN0105-100). Defined accessories for special measuring tasks Wide-range measuring device for all AC and three-phase networks with voltages from 65 to 500 V and frequencies from 15.4 to 420 Hz Loop and network impedance measurement with DC pre-magnetization Measurement of insulation resistance with nominal voltage, with variable or increasing test voltage Low-resistance measurement with automatic polarity reversal Testing of residual current devices and special RCD circuit breakers (selective S, SRCDs, PRCDs, Schukomat, Sidos, type G/R, AC, A, A-EV, F, F-EV, B, B+, B-MI) Testing of RDC-DD according to IEC 62955 and RCMB according to IEC 62752 Testing of residual current (RCD) protective circuits in IT networks Measuring the earthing resistance (network operation) Standard-compliant testing of e-charging stations according to IEC 61851-1 in conjunction with a suitable test adapter Auto function Test sequences USB interface Push-print function – sending the measured value after the measurement has been completed. Context-sensitive color graphic display Innovative and comprehensive operating concept Fast access to measuring and test functions via rotary switches and soft keys User-friendly No time-consuming replugging of the measuring cables required Modern data management Comprehensive data management concept in conjunction with the user software, including customer and measured value management, test sequences, logging Unique storage concept Creation of system structures – customer, system, machine, distributor, RCD, circuits, earthing electrodes, equipotential bonding bars, operating equipment and individual measuring points PUSH-PRINT function Sending the measured value via USB after the measurement has been completed Test sequences Creation of individual test sequences for the fast and safe testing of electrical systems Future-oriented connectivity Bidirectional data exchange (USB), connection of barcode scanner and USB push-print function. 1 x PROFiTEST MF
Property | Value |
Display: | digital |
Insulation resistance measurement: | yes |
Surge arrester test: | yes |
Loop resistance/impedance measurement: | yes |
Internal network resistance measurement: | yes |
RCD/FI test: | yes |
RCD/FI test with increasing Fault current: | yes |
RCD/FI analysis function: | yes |
Rotational field test: | yes |
Low-resistance measurement: | yes |
Earth measurement: | yes |
Selective earth measurement: | yes |
Earth loop measurement: | yes |
Specific earth measurement: | yes |
Measured value memory: | yes |
Interface: | yes |
Printer connection: | no |
Limit value display: | yes |
Resistances of insulating floors and walls: | yes |
Loop measurement without RCD/FI triggering: | yes |
Determination of short-circuit current/overcurrent protection devices: | yes |
Integrated printer: | no |
Remote control of the test device: | yes |
Insulation resistance measurement with ramp function: | yes |
Low resistance measurement with ramp function: | yes |
PRCD test type S, type K: | yes |
Testing of e-charging stations, simulation of vehicle status: | yes |
Structured measured value memory: | yes |