Current limiting relay capacitive 230V/120 microfarads. 1 normally open contact 10A/250VAC. No standby loss. For flush mounting. 45mm long, 45mm wide, 18mm deep. Maximum capacitive load 120 microfarads after rectifier (e.g. energy saving lamps and electronic ballasts) or 60 microfarads directly on the mains (e.g. parallel compensated fluorescent lamps). Limiting resistance 24 ohms, limitation duration approx. 15ms. The inrush current pulse of energy saving lamps, fluorescent lamps and compact fluorescent lamps is limited to 10A by briefly (approx. 15ms) switching on high load resistors (24 ohms). The current limiting relay is connected downstream of the relay contact of a switching device to be protected. Continuous load max. 600W, maximum switching frequency 600/h. Explanation of the capacitive load specification: The specification of the maximum capacitive load directly on the mains must be observed, for example, in the case of parallel-compensated fluorescent lamps or conventional ballasts. The capacitor per lamp that is connected parallel to the mains determines the correct dimensioning. The specification of the maximum capacitive load after the rectifier must be observed, for example, in the case of fluorescent lamps with electronic ballasts and energy-saving lamps. A replacement capacitance of approx. 10 microfarads per lamp can be expected.