LED universal dimming station 4-way REG housing 8 TE Intended use Switching and dimming of incandescent lamps, HV halogen lamps, dimmable HV LED lamps, dimmable compact fluorescent lamps, dimmable inductive transformers with LV halogen or LV LED lamps, dimmable electronic transformers with LV halogen or LV LED lamps Suitable for mixed loads up to the specified total power No mixed load operation of electronic and inductive transformers on the same load output Operation using sensor modules, touch sensor modules, 24 V touch sensors, 24 V touch sensor modules or non-illuminated installation buttons Installation on top hat rail according to DIN EN 60715 in sub-distribution board Operation of the device with universal power additives in combination with electronic transformers is not possible! To increase the power when operating electronic transformers, use Tronic power boosters. Product features Keypad for operating the dimming station Control of feedback LEDs at the control points. The dimming station has control outputs A1' ... A4' for this purpose. Electronic short-circuit protection with permanent shutdown after 7 seconds at the latest Electronic overtemperature protection Switch-on brightness can be set separately for each load output Switch-on brightness can be saved permanently Switch-on using a lamp-friendly soft start Switch-off using a dimming function Output power can be increased by connecting several outputs in parallel Power can be expanded using power add-ons (item no. ULZ 1755 REG) Connection for hotel card switch Central function Central ON, Central OFF: Switching the load outputs on or off together Parallel connection of two dimming stations or one dimming station and one relay station Automatic setting of the dimming principle that suits the load Optional accessories: LED compensation module, item no.: KM LED 230 U Hotel card switch function In combination with a hotel card switch (item no.: .. CARD ..), the light is switched on to the switch-on brightness after the hotel card is inserted. After the hotel card is removed, the light remains switched on for approx. 1 minute and the dimming station can be operated. After the time has elapsed, the light is dimmed to the minimum brightness within an adjustable time of approx. 30 seconds - 3 minutes and then switched off. The dimming station can only be operated again after the hotel card has been inserted. Nominal voltage: AC 230/240 V ~, 50/60 Hz Power loss: max. 20 W Standby power: max. 2 W Terminals -, + Control voltage: DC 24 V SELV Current load capacity: 80 mA Length of control cable: max. 100 m Number of control points Sensor module (item no.: SM 1608): max. 4 (also for relay/dimming stations connected in parallel) Touch sensor module (item no.: 4008 TSM): max. 4 (also for relay/dimming stations connected in parallel) Touch sensor modules 24 V AC/DC (normally open): depends on the touch sensor module, note the current consumption Switching inputs E1ON/OFF ... E4ON/OFF Control voltage: DC 24 V SELV Resistance Ri: 200 k Control outputs A1' ... A4' Control voltage: DC 24 V SELV Current carrying capacity: 10 mA Resistance Ra: 330 Mains / load outputs / hotel card switch Connection type: screw terminals single-wire: 1 x 1.5 ... 4 mm2 fine-wire without wire end ferrule: 1 x 0.75 ... 4 mm2 fine-wire with wire end ferrule: 1 x 0.5 ... 2.5 mm2 Connection switching inputs / control outputs / control points Connection type: screw terminals single-wire: 1.5 mm² fine-wire without Wire end ferrule: 1 mm² fine-stranded with wire end ferrule: 0.75 mm² Load outputs A1 ... A4 Contact type: Length of load cable per channel: max. 100 m Connected load per channel Incandescent lamps: 20 ... 150 W HV halogen lamps: 20 ... 150 W Electronic transformers: 20 ... 150 W Inductive transformers: 20 ... 150 VA HV LED lamps dimmable: typically 3 ... 30 W Compact fluorescent lamps dimmable: typically 3 ... 30 W Ohmic-capacitive: 20 ... 150 W Ohmic-inductive: 20 ... 150 VA Capacitive-inductive: not permitted Power reduction for every 5 °C exceeding 45 °C: -15 % Load outputs connected in parallel may only be used to 80 % capacity. Installation width: 144 mm (8 HP)